MIL-STD-1399-3008
5.3.8 Voltage and frequency modulation test. User equipment performance shall be evaluated under the voltage modulation and frequency modulation conditions specified in Table I, items 3 and 10, and further expanded in Table VII (see 3.3.3 and 3.4.4). The periodicity of voltage modulation should be considered to be longer than 1 cycle time at nominal frequency and less than 10 seconds. The periodicity of frequency modulation should be considered as not exceeding 10 seconds.
TA8LE VII. Voltage and frequency modulation test.
Voltage modulation |
Frequency modulation |
|||||||
Limit (%) |
Nominal (Vrms) |
Minimum (Vrms) |
Maximum (Vrms) |
Limit (%) |
Nominal (Hz) |
Minimum (Hz) |
Maximum (Hz) |
|
Type I, 3-phase |
2 2 |
115 440 |
112.70 431.20 |
117.30 448.80 |
0.5 |
60 |
59.7 |
60.3 |
Type I, 3-phase, grounded |
2 |
200 |
196.00 |
204.00 |
0.5 |
60 |
59.7 |
60.3 |
Type I, 1-phase |
2 2 |
115 440 |
112.70 431.20 |
117.30 448.80 |
0.5 |
60 |
59.7 |
60.3 |
Type I, 1-phase, grounded |
2 |
115 |
112.70 |
117.30 |
0.5 |
60 |
59.7 |
60.3 |
Type II, 3-phase |
2 2 |
115 440 |
112.70 431.20 |
117.30 448.80 |
0.5 |
400 |
398 |
402 |
Type II, 1-phase |
2 2 |
115 440 |
112.70 431.20 |
117.30 448.80 |
0.5 |
400 |
398 |
402 |
Type III, 3-phase |
1 1 |
115 440 |
113.85 435.60 |
116.50 444.40 |
0.5 |
400 |
398 |
402 |
Type III, 3-phase, grounded |
1 |
200 |
198.00 |
202.00 |
0.5 |
400 |
398 |
402 |
Type III, 1-phase |
1 1 |
115 440 |
113.85 435.60 |
116.15 444.40 |
0.5 |
400 |
398 |
402 |
Type III, 1-phase, grounded |
1 |
115 |
113.85 |
116.15 |
0.5 |
400 |
398 |
402 |
5.3.8.1 Apparatus. The following apparatus is recommended for performing this test:
a. Power source of required capacity and range of voltage and frequency adjustments. A power source with a capability of having an independently programmable voltage and frequency output is recommended.
b. Voltmeters (true rms) - ±0.5 percent accuracy. c. Frequency meter - ±0.5 Hz accuracy.
d. Storage oscilloscope having � 500 kHz response per channel.
e. Current and potential transformers and probes as required. f. Temperature meter - ±0.5 °C accuracy.