MIL-STD-1399-300B
60 450 or 120
50 Quarter Load
On Generator
40
30
20
Half Load
On Generator
400 or 107
350 or 93
300 or 80
250 or 67
Full Load
On Generator
10 200 or 53
0
0 5 10 15 20 25
Time (Seconds)
FIGURE 8. Voltage and frequency decay characteristics on loss of prime mover for typical steam turbine driven generator set, Type I, 60-Hz electric power system.
5.1.3.4 Power interruption, Types II and III electric power system. Loss of input power to 601400 Hz motor generator (MG) sets will activate control circuits provided with MG sets which trip the MG circuit breaker. This interrupts power to 400 Hz loads in a few milliseconds. Upon loss of 60 Hz power to solid-state frequency changers, the 400 Hz power is interrupted within 2 msec by controls in the frequency changer. Voltage and frequency monitors that are provided separately from conversion equipment controls, trip the MG 400 Hz output circuit breaker when the output voltage or frequency reach those values specified in 5.1.5.2 or 5.1.5.3 as applicable to the type power provided.
5.1.4 Phase sequence. Standard phase sequence for three-phase AC systems in the U.S. Navy is in the following order: AB, BC, and CA. For grounded systems, the phase sequence is AN, BN, CN.