MIL-STD-1399-3008
9
8
7
6
5
4
Type lll
115 Vac
3
2
Type ll
115 Vac
Type lll
440 Vac
Type ll
440 Vac
1
0
1 10 100 1000
lnput Power (kW) Rating of User Equipment
FIGURE 22. Surge current limits for load equipment using Type II or III power.
5.2.11 Insulation resistance. When un-energized, user equipment shall tolerate the application of 500 VDC by a megohmmeter insulation resistance tester between each power conductor and ground without equipment damage, arc-over, degradation, or abnormal operation. NSTM Chapter 300 procedures may be used as a guide. The resistance to ground value as measured by the megohmmeter shall be equal to or greater than 10 Mohms as identified in MIL-E-917.