MIL-STD-1399-3008
5.2.10 Surge/inrush current. User equipment shall be constructed to limit the ratio of surge current to normal operating current. The ratio of the maximum surge/inrush peak current to the full nominal load rms current shall be limited to the value determined from Figure 21 for Type I, 60 Hz electric power and Figure 22 for Types II and III,
400 Hz electric power. Load sequencing may be required to maintain an acceptable user voltage envelope at the
user interface. Surge/inrush current shall be measured, recorded, and evaluated when energizing the user equipment at the nominal input voltage when the voltage source sine-wave passes through 0 degrees for inductive load equipment or when the sine-wave passes through 90 degrees for capacitive load equipment. Multiple surge/inrush
current occurrences observed on the same event shall be addressed and evaluated individually to determine
compliance with the above requirements.
10
9
8
7
Type I
115 Vac
6
5
Type I
440 Vac
4
3
2
1
0
1 10 100 1000
Input Power (kW) Rating of User Equipment
Figure 21. Surge current limits for load equipment using Type I power.