5.2.9.3 400 Hz user equipment greater than or equal to 0.2 kVA. The operation of user equipment or the aggregate with power ratings > 0.2 kVA shall not cause single harmonic line current or current of any frequency above the fundamental at 400 Hz to 13.33 kHz to be generated that are greater than the limit line set at 3 percent of the unit's full rated load fundamental current. Additionally, harmonic line current or current of any frequency above
13,334 Hz through 20 kHz shall not exceed the limit line set at 40,000/f percent of the user equipment's full load fundamental current, where f is the frequency. This is shown in Figure 19. User equipment, for the purposes of this requirement, shall be defined as a system with a standalone unit or the aggregate of a system with multiple like units on a single bus, e.g. lighting source power supplies. The rating of equipment with multiple power inputs from the same interface shall be the summation of all the power inputs under steady-state conditions.
Percent
of 400 Hz
Fundamental
Current (A)
FIGURE 19. Limit line for currents at frequencies greater than 400 Hz for equipment greater than or equal to 0.2 kVA.
31